Permit Number: T04CM03251
Parcel: 110050380

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03251
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2004 JIM TATE ENGINEERING REVIEW Approved
07/14/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Based on the provided information, the existing water meter is too small to support the proposed load. Reference Section 610.4, UPC 1994.
07/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03251 DENIED 7/15/04

1. Provide electrical design, including but not necessarily limited to: identification of Circuit numbers and location of equipment to be removed; power requirements for new Insta-hot; disconnect for new Insta-hot and exhaust fan; panel and circuit number for new equipment; specification of conductor and conduit size and type.
07/15/2004 ROBERT SHERRY WATER REVIEW Approved
07/15/2004 JIM EGAN FIRE REVIEW Approved
07/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/20/2004 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
07/20/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2004 BETH GRANT OUT TO CUSTOMER Completed