Permit Number: T04CM03218
Parcel: 110102660

Address:
3140 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03218
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2004 JIM EGAN FIRE REVIEW Approved
07/13/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/13/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water calculations based on Table 6-4. Reference Section 610.4, UPC 1994.
2. Include all of the fixtures when determining the total fixture count and demand. Reference Section 610.1, UPC 1994.
3. Provide access and working space for the water heater per Section 511.0, UPC 1994.
07/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/14/2004 ROBERT SHERRY WATER REVIEW Approved
07/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy calculations updated to include the mechanical and lighting.
07/23/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/23/2004 CAGUILA1 WWM REVIEW Needs Review