Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03218
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/13/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/13/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 07/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide water calculations based on Table 6-4. Reference Section 610.4, UPC 1994. 2. Include all of the fixtures when determining the total fixture count and demand. Reference Section 610.1, UPC 1994. 3. Provide access and working space for the water heater per Section 511.0, UPC 1994. |
| 07/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 07/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide energy calculations updated to include the mechanical and lighting. |
| 07/23/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/23/2004 | CAGUILA1 | WWM | REVIEW | Needs Review |