Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03210
Parcel: 11615077C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03210
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2004 JIM EGAN FIRE REVIEW Approved
07/15/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/15/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
07/15/2004 ROBERT SHERRY WATER REVIEW Approved
07/15/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
07/15/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/15/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/16/2004 GERRY KOZIOL WWM REVIEW Approved
07/16/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03210 DENIED 7/15/04
1. Circuit 4, with 18' of track lighting, would have 1350VA, and 1,688 VA at continuous load.
2. Circuit 5, with 16' of track lighting, would have 1200VA, and 1500 VA at continuous load.
3. Circuit 11, consistent with nomenclature, would be calculated at continuous load.
4. 20A CB too small for 15000VA AC.