Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03210
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 07/15/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/15/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/15/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/15/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/15/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/15/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 07/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03210 DENIED 7/15/04 1. Circuit 4, with 18' of track lighting, would have 1350VA, and 1,688 VA at continuous load. 2. Circuit 5, with 16' of track lighting, would have 1200VA, and 1500 VA at continuous load. 3. Circuit 11, consistent with nomenclature, would be calculated at continuous load. 4. 20A CB too small for 15000VA AC. |
| 07/16/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |