Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03200
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/28/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03200 DENIED 7/28/04 1. Show volt-ampere count on each branch circuit. 2. Provide load calculations per NEC Article 220. See NEC 220.3 (B) (9) for receptacle loads. See Part I for Feeders and Services. 3. Specify conduit type and size. 4. Specify conductor type and size. 5. Provide cut sheet/fixture schedule for lighting fixtures on Circuit 5. Demonstrate compliance with the Outdoor Lighting Ordinance. |
| 07/28/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the route, and termination of the condensate drain. Clarify the material to be used for the piping. Reference Section 307, IMC 2000. 2. Enlarge the specifications for the new heat pump to at least 10 points. 3. Show how the supply diffusers are to be balanced. 4. Indicate how many joists are being spanned by the redwood sleepers supporting the heat pump. |