Permit Number: T04CM03200
Parcel: 124070400

Address:
745 E 9TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03200
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/28/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03200 DENIED 7/28/04
1. Show volt-ampere count on each branch circuit.
2. Provide load calculations per NEC Article 220. See NEC 220.3 (B) (9) for receptacle loads. See Part I for Feeders and Services.
3. Specify conduit type and size.
4. Specify conductor type and size.
5. Provide cut sheet/fixture schedule for lighting fixtures on Circuit 5. Demonstrate compliance with the Outdoor Lighting Ordinance.
07/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the route, and termination of the condensate
drain. Clarify the material to be used for the piping. Reference Section 307, IMC 2000.
2. Enlarge the specifications for the new heat pump to at least 10 points.
3. Show how the supply diffusers are to be balanced.
4. Indicate how many joists are being spanned by the redwood sleepers supporting the heat pump.