Permit Number: T04CM03200
Parcel: 124070400

Address:
745 E 9TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03200
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
07/12/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/22/2004 JIM EGAN FIRE REVIEW Approved 1. NEED CODE REVIEW CHECKLIST.
2. ONE-HOUR FIRE BARRIER REQUIRED BETWEEN OFFICE/STORAGE. OPENINGS PROTECTED WITH ONE-HOUR FIRE RATED ASSEMBLIES.
07/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/23/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied
07/23/2004 ROBERT SHERRY WATER REVIEW Approved
07/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03200 DENIED 7/23/04
1. Complete the electrical design providing lighting fixutre schedule cut sheets, panel & circuit designations, completed panel schedule.
2. Provide actual specifications, not just Code references.
3. See the attached for Electrical Permitting Requirements.
4. Design shall comply with NEC 2002 and IECC 2000.
07/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a design based on the 2000 International Mechanical Code, not the IRC.
2. Provide ventilation calculations for the new areas. Reference Section 403, IMC 2000.
3. Show size, route, and termination of the condensate drain. Reference Section 307, IMC 2000.
4. Provide specifications for the new heat pump. Show the weight of the unit (including any accessories) and show how it is being supported on the roof.
07/28/2004 CAGUILA1 WWM REVIEW Passed