Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03162
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show how the water distribution piping was sized. (Clarify drawing - it appears that the new fixtures are being supplied from an existing 3/4" cold watere pipe.) Reference Section 103.2.3, UPC 1994. 2. Revise the vent for the janitor's sink so that it does not originate at the tailpiece of the sink. 3. Arizona State law requires that the Registrant's seal be signed and dated. |
| 07/21/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Arizona State law requires that the Registrant's seal be signed and dated. |
| 08/02/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/02/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/02/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |