Permit Number: T04CM03162
Parcel: 127090080

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03162
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations to show how the water
distribution piping was sized. (Clarify drawing - it appears that the new fixtures are being supplied from an existing 3/4" cold watere pipe.) Reference Section
103.2.3, UPC 1994.
2. Revise the vent for the janitor's sink so that it does not originate at the tailpiece of the sink.
3. Arizona State law requires that the Registrant's seal be signed and dated.
07/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Arizona State law requires that the Registrant's seal be signed and dated.
08/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/02/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/02/2004 TAMI ACHONG OUT TO CUSTOMER Completed