Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM03162
Parcel: 127090080

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03162
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2004 JIM TATE ENGINEERING REVIEW Approved
07/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Increase the size of the fonts on detail 1/P-12
to a minimum of 10 Points.
2. Provide a legible Seal for the drawings.
3. Provide a vent for the drinking fountain. Reference Section 901.0, UPC 1994.
4. Provide cleanouts for KS-1and JS. Reference Section 707.4, UPC 1994.
5. Provide calculations to show how the water distribution piping was sized. Reference Section 103.2.3, UPC 1994.
6. Include the janitor's sink, JS, on the fixture schedule.
07/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, route, and termination of the condensate drains form the rooftop units.Reference Section 103.2.3, UPC 1994.
2. Clarify where EF-2 is located. Reference Section 103.2.3, UPC 1994.
3. Increase the size of the fonts on detail 2/M-2 to a minimum of 10 Points.
4. Provide a legible Seal for the drawings.
07/09/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/09/2004 ROBERT SHERRY WATER REVIEW Approved
07/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/09/2004 JIM EGAN FIRE REVIEW Approved
07/09/2004 DAN CASTRO ZONING REVIEW Approved
07/21/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2004 BETH GRANT OUT TO CUSTOMER Completed