Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM03156
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the proposed Type I hood to show that the scheduled exhaust fan is suitable for its intended use. Reference Section 106.3.1, IMC 2000. 2. Show how the hood is to be mounted to the building structure to comply with Section 507.6, IMC 2000. 3. Mechanical general note #9 requires the contractor to perform an engineering analysis of the gas appliance vent installation. Provide a design for the vents if they are part of this project. Reference ARS 32-121. |
| 04/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The submitted plumbing drawings are incomplete and do not appear to address the project presented on the architectural drawings. Reference Section 103.2.3, UPC 1994. 2. Revise the provided riser diagrams for the water and waste systems to clarify which fixtures are being installed. Reference Section 103.2.3, UPC 1994. 3. Revise the drain of the hand sink to be directly connected to the waste system. Reference Section 304.0, UPC 1994. This comment does not appear to have been addressed. |
| 04/22/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/25/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/25/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |