Permit Number: T04CM03156
Parcel: 11449036C

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM03156
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2005 TACHONG1 WWM REVIEW Needs Review
07/09/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03156 DENIED 7/9/04

1. EF-1 is listed as 1.5 HP on Sheet M1.1 and panel schedule. Is ¾ HP on Wiring Diagram. If this is a 1.5 HP motor the 5A fuse may not allow it to start. Please clarify.
2. Please re-evaluate the #12 feeder to EF-1, protected by the 50A CB, for protection at its ampacity.
3. There are (2) AC-1 on Wiring Diagram, and no EC-1. Please clarify.
4. If the FRN-R 5 fuse is intended to protect EC-1, it may not allow this ¾ HP motor to start.
07/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagrams for the water and waste systems. Reference Section 103.2.3, UPC 1994.
2. Provide alisted flow control device for the 3-compartment sink drain to the grease trap. Reference Section 1011.2, UPC 1994.
3. Revise the drain of the hand sink to be directly connected to the waste system. Reference Section 304.0, UPC 1994.
07/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Submit shop drawings and calculations, stamped by an Arizona Registered engineer for approval, to the City of Tucson Development Services Department PRIOR to erection of the Type I hood. Shop drawings shall be reviewed and bear the approval stamp of the Architect or Engineer of Record prior to submission to the City of Tucson Development Services Department.
2. Provide sufficient makeup air to the kitchen, in addition to the makeup air supplied to the compensating hood, to comply with the requirements of Section 508.1, IMC 2000.
3. Show how the hood is to be mounted to the building structure to comply with Section 507.6, IMC 2000.
4.Provide installation details for the grease duct to show compliance to Section 506, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2005 TAMI ACHONG OUT TO CUSTOMER Completed