Permit Number: T04CM03145
Parcel: 108193140

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03145
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
07/08/2004 DAN CASTRO ZONING REVIEW Approved
07/09/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the water distribution piping was sized. Reference Section 103.2.3, UPC 1994.
2. Revise the T&P relief pipe to comply with the listing requirements of the T&P valve. "Excessive length over 30' (9.14m), or use of more than four elbows or reducing discharge line size will cause a restriction and reduce the discharge capacity of the valve." (Watts Regulator Co., "Correct Installation of T&P Relief Valves")
07/09/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/09/2004 ROBERT SHERRY WATER REVIEW Approved
07/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a Type I hood for the range. Reference Section 507.2.2, IMC 2000.
07/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
07/22/2004 LLESNY1 WWM REVIEW Needs Review
07/22/2004 LLESNY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2004 LISA LESNY OUT TO CUSTOMER Completed