Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/08/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
07/08/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
07/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the water distribution piping was sized. Reference Section 103.2.3, UPC 1994. 2. Revise the T&P relief pipe to comply with the listing requirements of the T&P valve. "Excessive length over 30' (9.14m), or use of more than four elbows or reducing discharge line size will cause a restriction and reduce the discharge capacity of the valve." (Watts Regulator Co., "Correct Installation of T&P Relief Valves") |
07/09/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/09/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a Type I hood for the range. Reference Section 507.2.2, IMC 2000. |
07/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/22/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
07/22/2004 | LLESNY1 | FIRE | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/22/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |