Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM03136
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Specify on site plan buildings of proposed work. 2. Provide complete allowable area calculations for buildings to be reclassified. Include mixed-use calculation. 3. Provide analysis for non-separated uses. 4. Provide occupancy classifications for uses other than classrooms. I.e.… chapel, multi-purpose rooms etc… 5. Show accessible route from each building to accessible bathrooms. 6. Provide cost breakdown for 20% of the alteration being utilized for accessibility. 7. Property line splits buildings. Provide documentation parcels have been joined or show required party wall per Table 705.4 IBC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 07/19/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |