Permit Number: T04CM03136
Parcel: 138190430

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM03136
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Specify on site plan buildings of proposed work.
2. Provide complete allowable area calculations for buildings to be reclassified. Include mixed-use calculation.
3. Provide analysis for non-separated uses.
4. Provide occupancy classifications for uses other than classrooms. I.e.… chapel, multi-purpose rooms etc…
5. Show accessible route from each building to accessible bathrooms.
6. Provide cost breakdown for 20% of the alteration being utilized for accessibility.
7. Property line splits buildings. Provide documentation parcels have been joined or show required party wall per Table 705.4 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2004 BETH GRANT OUT TO CUSTOMER Completed
07/19/2004 ANGIE SHOFFSTALL REJECT SHELF Completed