Permit Number: T04CM03119
Parcel: 12604012B

Address:
4414 E 2ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03119
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2004 Jim Egan FIRE REVIEW Approved
07/27/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide roof drainage calculations and plans. Provide overflow protection for the roof. Clarify the effect of the existing roof as a possible contributing area for rain collection for the new roof. Reference Appendix D, UPC 1994.
07/27/2004 ROBERT SHERRY WATER REVIEW Approved
07/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations. Reference Section 101.2, International Energy Conservation Code 2000.
07/28/2004 GERRY KOZIOL WWM REVIEW Passed
07/29/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved APPROVED FUP T04OT01418
08/09/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8-11-04
ACTIVITY NUMBER: T04CM03119
PROJECT NAME: WELLNESS CENTER ADDITION TO B'NAI B'RITH COVENANT HOUSE
PROJECT ADDRESS: 4414 E 2ND ST
ARCHITECT / ENGINEER: JACQUES GERSTENFELD
PROJECT REVIEWER: CHRISTY FOREMAN
PHONE:791-5550 EXT 1108
EMAIL: CFOREMA1@CI.TUCSON.AZ.US

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1. Submit a complete code analysis. Clarify occupancy I-1 or R-2. See table 503 for height and area allowable. Separated use or non-separated use? Clarify allowable areas based on existing areas that additional square footage can be added.
2. Justify / clarify occupancy load for room added. Table 1003.2.2.2
3. What is on the other side of the wall from the exercise room. Clarify that existing bldg. Still meets code section 1009. Clarify no emergency exits for sleeping rooms are being blocked off.
4. Need clarification that existing building does not require to use this room for egress. See code section 1004.2.3 - new double door has a cylinder lock on the exterior, which could prevent egress.
5. 1003.3 Clarify door hardware height.
6. Ramp - conform to section 1003.3.4.1 & 1003.3.4.9.
7. Sht. A-5 specify pre-fabricated truss on roof framing plan - see structural calculations.
8. Provide acoustical tile attachment detail.
08/17/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide detailed instructions on plans for the new feeder connection to the load side of the existing breaker. Demonstrate that the listing of the original equipment will not be violated.
2. Provide load calculations on the plans, demonstrating that the service will not be overloaded.
08/26/2004 Peter McLaughlin ZONING REVIEW Denied Approved site plan required.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2004 TAMI ACHONG OUT TO CUSTOMER Completed
08/27/2004 ANGIE SHOFFSTALL REJECT SHELF Completed