Permit Number: T04CM03105
Parcel: 128090020

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03105
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2004 JIM EGAN FIRE REVIEW Approved
07/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Specify the types of backflow devices (if any) to be used for each equipment connection.
07/07/2004 DAN CASTRO ZONING REVIEW Approved
07/07/2004 ROBERT SHERRY WATER REVIEW Approved
07/07/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/09/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/09/2004 CAGUILA1 WWM REVIEW Needs Review
07/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03105 DENIED 7/9/04

1. Panel A Phase A is overloaded at 268 A.
2. Feeder to Panel B is undersized at ampacity of 85A. Phase A would draw 87 amps.
3. Provide load calculations for service.