Permit Number: T04CM03104
Parcel: 13314227B

Address:
1400 N WILMOT RD

Review Status: Completed

Review Details: SITE

Permit Number - T04CM03104
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2004 Jim Egan FIRE REVIEW Denied 1. Fire hydrants required submit approved COT Water Plan.
2. Fire protection water supply shall not be interrupted atn any time that the building is occupied.
3. Fire access roadway and fire lane signs reqired.
07/15/2004 Andrew Connor NPPO REVIEW Denied Submit previously approved site and landscape plans and if applicable calculations of past expansions.
07/15/2004 Andrew Connor LANDSCAPE REVIEW Denied Expansion of existing development per LUC3.7.1.2.B

1. On sites where the gross floor area of the existing building(s) is more than ten thousand (10,000) square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows.

a. If the expansion is less than twenty-five (25) percent, the requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations at the time the existing development received zoning approval.

b. If the expansion is twenty-five (25) percent or greater or if expansions as of February 15, 1991cumulatively result in a twenty-five (25) percent or greater expansion in land area, floor area, lot coverage, or vehicular use area, the requirements of this Division apply to the entire site.

Submit previously approved site and landscape plans and if applicable calculations of past expansions.
07/19/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied On sheet C1.1, provide the percent slope and direction of slope for the accessible ramp detail provided. (D.S. 2-02.2.1.A.8) (ICC/ANSI A-117-1998 Sec. 405)
07/19/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were
addressed. (CODE SECTION/ DEVELOPMENT STANDARD)

1. The following comments are based on a 1.4 % building area expansion resulting in a full code compliance review for the expansion area only. List the percent expansion on sheet G2.1.
(D.S. 2-02.2.2.A.6)

2. On sheet A0.4, dimension the vehicle parking space depth. Refer to LUC Sec. 3.3.7.2 and Table 3.3.7-I.

3. A minimum distance of five (5) feet for a pedestrian refuge area must be maintained between the building (addition) and the one-way PAAL. (D.S. 3-05.2.2.B.1)

4. On sheet C1.1, provide the percent slope and direction of slope for the accessible ramp detail provided. (D.S. 2-02.2.1.A.8) (ICC/ANSI A-117-1998 Sec. 405)

5. Dimension the length and width of the access aisle delineated by keynote 9 on sheet A0.4.

6. Dimension the width of the one-way PAAL located between the access aisle and the closest point of curb on sheet A0.4

7. Review of this plan by the Zoning Review Section may be done over the counter. Please contact me at the number below to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
08/03/2004 Loren Makus ENGINEERING REVIEW Denied DATE: August 4, 2004
TO: Metro Permit Express
SUBJECT: Site Plan: El Dorado Hospital Addition
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM03104

SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on August 4, 2004. It was not approved. Please address the following comments.

Site Plan Comments:

DS 2.1.A.5 Provide lot dimensions and bearings on the site plan.
DS 2.1.A.10 Provide sight visibility triangles at the driveways from the road along the north property line.
DS 2.1.A.16 Show drainage patterns and existing grades at various locations throughout the site.
DS 2.1.A.19 Dimension the adjacent right-of-way and show existing and future right-of-way locations.
DS 2.1.A.32 Show refuse container locations.

Revise the Site Plan, to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed.
Loren Makus
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2004 BETH GRANT OUT TO CUSTOMER Completed
08/10/2004 ANGIE SHOFFSTALL REJECT SHELF Completed