Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03032
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/14/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/15/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03032 DENIED 7/13/04 1. Change Electrical Specification #1 from "1999 NEC" to "2002 NEC". 2. Service load calculations total 449.3. This exceeds the 400A service capacity and the 385A ampacity of the 750 MCM Al conductors. DENIED 7/14/04 Load calculation uses wrong figure for new load. |
| 07/26/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |