Permit Number: T04CM03032
Parcel: 12217002B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03032
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/14/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03032 DENIED 7/13/04

1. Change Electrical Specification #1 from "1999 NEC" to "2002 NEC".
2. Service load calculations total 449.3. This exceeds the 400A service capacity and the 385A ampacity of the 750 MCM Al conductors.

DENIED 7/14/04 Load calculation uses wrong figure for new load.
07/26/2004 GERRY KOZIOL WWM REVIEW Approved