Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03013
Parcel: 127051410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1/06/2006

1) Specify the size of windows in the bedrooms. They shall
comply to the emergency escape requirement section
1025.1,1025.2,1025.2.1, and 1025.3.
2) Note on plans what the S inscribed in a circle represents.
01/12/2006 JOSE ORTIZ ENGINEERING REVIEW Denied A stamped approved Site Plan required prior to approval.
01/20/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide Ground-Fault Circuit Interrupter Protection for exterior and countertop receptacles (Apt 1). Reference NEC 210.8.
2. Show EF-1 through EF-4 on Electrical Plans. Show Disconnect, Panel and Circuit Number, and account for in load calculations.
3. Lighting fixtures are on Circuit C4. According to the panel schedule, small appliances are indicated on this circuit.
4. Document TEP contact person for Available fault current. According to SR-510 apartments do not fall under the category of services for which the facilities will be necessarily designed such that maximum fault current does not exceed 10,000A. Provide fault calculations, and AFC at equipment, as appropriate...
02/20/2006 DAVID RIVERA ZONING REVIEW Denied 02/20/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The building plans have been reviewed but cannot be approved at this time. An approved and stamped site plan must is required prior to approval of the building plans.

2. Zoning will re-review the building plans once the plans have been approved by the building reviewers and review for compliance with the approved and stamped site plan.
12/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The controlling code for this project is the 2003 Uniform Plumbing Code as amended by the City of Tucson.
2. Provide water pressure and water pipe sizing calculations to show how the water piping and the water meter were sized. Reference Section 610.1, UPC 2003.
3. Comment not addressed. Modify the site drawing to show the size, material, and route of the building water supply along with the location and size of the water meter. Reference Section 103.2.3, UPC 2003.
4. Comment not addressed. Modify the site drawing to show the size, route, material and slope of the building drain. Reference Section 103.2.3, UPC 2003.
5. Revise the waste and vent riser diagram to include all of the pipe sizes and coordinate the diagram with the plumbing plan. Reference Section 103.2.3, UPC 2003.
6. Show that the plumbing vents comply with Section 904.0, UPC 2003. (A note on the drawing is not sufficient)
7. Comments not addressed. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 2003.
8. Comment not addressed. Provide fixture descriptions for all plumbing fixtures. Reference Section 103.2.3, UPC 2003. (Please read Section 103.2.3, UPC 2003)
9. Comment not addressed. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003.
10. Revise the note on detail 2/MP-1 regarding the termination of the T&P relief pipe; it may not terminate at a trap. Reference Section 608.5, UPC 2003.
11. Comment not addressed. Provide ½" insulation on the first eight feet of supply and discharge piping for the water heater. Reference Section 804.5, IECC 2000.
12. Specify the material to be used for the gas piping; "steel pipe" is not sufficient. See Section 1209.5.2.2, UPC 2003.
13. Revise the size of the gas piping per Sections 1209.4 and 1209.4.3, UPC 2003. Include the demand for the future gas-fired furnace in apartment #3.
14. Show that the required combustion air openings exist for the water heater in apartment #3. Reference Section 507, UPC 2003, as amended by the City of Tucson.
15. Show that the specified combustion air louvers provide the net free area needed to meet the requirements of Table A, Chapter 5 of the local amendments to the 2003 UPC. Reference Section 507.9, UPC 2003 as amended by the City of Tucson
16. If the furnace is installed in apartment #3, provide adequate maintenance access to the water heater. Reference Section 310.4, UPC 2003.
12/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The controlling code for this project is the 2003 International Mechanical Code as amended by the City of Tucson.
2. Revise the provided flue calculations to include only the water heater flue. The specified gas furnace is a direct-vent, condensing furnace and its flue may not be combined with any other gas-fired appliances. (The clothes dryer does not have a flue; it has an appliance vent, which is to be sized per Section 504, IMC 2003.) Provide a detail showing how the furnaces and water heaters are to be installed. Show how the condensate from the flue is to be handled. Reference Section 103.2.3 UPC 2003.
3. Show how the condensate from the furnace flue is to be handled. Reference Section 307.1, IMC 2003.
4. Show the size and routing of the condensate drains. Clarify the termination of the condensate drains (Apartment #2 shows the condensate terminating at the trap of the kitchen sink, which is not allowed; Apartment #1 shows the condensate terminating along a blank wall with no associated piping.). Reference Section 307, IMC 2003 as amended by the City of Tucson.
5. Revise the duct insulation specification and show the R-value for the duct insulation on the drawings. The minimum insulation for ducts located in unconditioned spaces within the building envelope shall be in accordance with the requirements of Table 503.3.3.3, IECC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2006 GBONILL1 OUT TO CUSTOMER Completed