08/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03009 DENIED 8/20/04
1. Plot exact location of new J-box on plans, such that compliance with NEC 240.21 may be verified.
2. Second time at counter j-box located, but is in violation of 240.21. 62' tap exceeds 25' limit.