Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM03009
Parcel: 11516040B

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM03009
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03009 DENIED 8/20/04
1. Plot exact location of new J-box on plans, such that compliance with NEC 240.21 may be verified.
2. Second time at counter j-box located, but is in violation of 240.21. 62' tap exceeds 25' limit.