Permit Number: T04CM03009
Parcel: 11516040B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03009
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2004 JIM EGAN FIRE REVIEW Approved
07/01/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/01/2004 JIM TATE ENGINEERING REVIEW Approved
07/02/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/02/2004 ROBERT SHERRY WATER REVIEW Approved
07/02/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TO4CM03009 DENIED 7/8/04
1. Provide disconnects for Evaporative coolers and pumps.
2. Considering continuous load, largest motor, and feed to L1, the load on Panel H1 appears to be 12,020 VA, 9550 VA, and 9770 VA, respectively.
3. The GND from the new transformer to Panel L1 shall be sized at #4 per NEC Table 250-66.
4. Show total load calculations for service.
5. Show capacity of service.
6. Show available fault current at service.
7. Show available fault current at panels H1 and L1.
07/22/2004 GERRY KOZIOL WWM REVIEW Approved
07/22/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2004 LISA LESNY OUT TO CUSTOMER Completed