Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03009
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/01/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
07/01/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
07/01/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
07/02/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
07/02/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/02/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
07/15/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TO4CM03009 DENIED 7/8/04 1. Provide disconnects for Evaporative coolers and pumps. 2. Considering continuous load, largest motor, and feed to L1, the load on Panel H1 appears to be 12,020 VA, 9550 VA, and 9770 VA, respectively. 3. The GND from the new transformer to Panel L1 shall be sized at #4 per NEC Table 250-66. 4. Show total load calculations for service. 5. Show capacity of service. 6. Show available fault current at service. 7. Show available fault current at panels H1 and L1. |
07/22/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
07/22/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/09/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |