Permit Number: T04CM03007
Parcel: 117020120

Address:
1023 N 1ST AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T04CM03007
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2004 Andrew Connor NPPO REVIEW Passed
07/08/2004 GERRY KOZIOL WWM REVIEW Approved
07/27/2004 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM03007
07/28/04
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. LABEL ALL ROOMS AND SPACES. IS BASEMENT A HABITAL ROOM OR UNFINISHED BASEMENT? CLARIFY.

2. PROVIDE THE LOCATIONS OF TEMPERED GLASS PER R308.4. REQUIRED AT STAIRS AND LANDING.

3. SHOW COMPLIANCE WITH R310 PROVIDING EGRESS FROM BEDROOMS.
- MAXIMUM SILL HEIGHT OF 44"--------CLEARLY INDICATE FOR LOWER LEVEL BEDROOM
- MINIMUM NET CLEAR DIMENSIONS OF OPENING OF 24" HEIGHT BY 20" WIDTH.--------LOWER LEVEL BEDROOM INDICATES 2850 DH WINDOW, ELEVATIONS AND CROSS SECTION INDICATE A 2840 DH WHICH DOES NOT MEET THE 24" HEIGHT OPENING REQUIREMENT-----CLARIFY

4. THE WALLS AND SOFFITS OF THE ENCLOSED SPACE UNDER STAIRS SHALL BE PROTECTED ON THE ENCLOSED
SIDE WITH ½" GYPSUM BOARD PER R314.8.

5. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

6. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A
CLEAR SPACE IN FRONT OF NOT LESS THAN 21" PER R307.2 (FIGURE).

7. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.

STRUCTURAL PLANS:

1. PROVIDE POSITIVE CONNECTION AT INTERIOR BEARING WALL --------STUDS TO PLATE, PLATE TO I-JOIST, ETC.

2. LOWER LEVEL WALL FRAMING PLAN INDICATES BWP AT MASONRY WALL? CLARIFY.

3. NOTCHING OF TOP OF I-JOIST FOR STEPS NOT ALLOWED. SEE MFG. SPECS.

PLUMBING PLANS:

1. INDICATE SIZE AND LOCATION OF MAIN WATER LINE. ADDITIONAL FIXTURE MAY OR MAY NOT REQUIRE A LARGER MAIN WATER LINE. INDICATE LOCATION OF EXISTING WATER HEATER AND WHAT SIZE LINES NEW WATER LINES ARE TYING INTO. PROVIDE MAXIMUM DEVELOPED LENGTH-----80' DOES NOT APPEAR TO BE CORRECT.

MECHANICAL PLANS:

1. THERE IS NO RECORD OF A PERMIT BEING OBTAINED FOR THE NEW FURNACE/AC. CAN BE INCLUDED ON THIS PLAN. SEE BELOW.

2. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.
3. IF THE HEATING OR AIR CONDITIONING EQUIPMENT IS LOCATED IN THE ATTIC, SHOW LOCATION OF ACCESS,
CATWALK AND WORKING PLATFORM. SHOW PROVISIONS FOR AND ROUTE OF SECONDARY CONDENSATE
DRAIN PER M1305.1.3.

ELECTRICAL PLANS:

1. INDICATE THE LOCATION OF CONVENIENCE OUTLET AND LIGHT SWITCH FOR ATTIC HEATING AND AIR
CONDITIONING EQUIPMENT PER E3801.11 AND E3803.4.

2. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 1112
08/10/2004 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Dan Wilhelm
1023 N. 1st Avenue
Tucson, AZ 85719


FROM: Peter McLaughlin
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT:
T04CM03007
Addition
1023 N. 1st Avenue

TRANSMITTAL: August 11, 2004

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. All lettering must be a minimum of 12 point (0.12"). Revise all lettering and dimensions which do not meet this minimum standard for microfilming/archiving. Note: Further comments may be necessary once all dimensions and text are legible on the lot plan.

2. Add the site zoning (HR-2) and adjacent zoning (also HR-2) on all sides of the subject property to the site plan. DS 2-02.2.1.A.28

3. Add a north arrow to the site plan. DS 2-02.2.1.A.1

4. After all revisions are made a re-stamping of the Historical Preservation Zone (HPZ) approval must be obtained on the plan prior to approval by zoning review.



If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2004 BETH GRANT OUT TO CUSTOMER Completed
08/12/2004 SUE REEVES REJECT SHELF Completed