Permit Number: T04CM02971
Parcel: 137055220

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02971
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the medium pressure gas pipes were sized; a note on the one-line gas diagram indicates an outlet pressure of 2 PSIG at the meter but note 3 indicates that Table 12-6 (5 PSIG) was used for sizing. If the piping was sized using Table 12-4 (2PSIG), correct the last section of medium pressure pipe to 1-1/4" (717 CFH @ 350 feet). Reference Section 1217.0, UPC 1994.
08/13/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The exhaust requirements for Type I hoods is determined by the type of equipment placed under the hood. According to the equipment schedule, a chip fryer is located under hood T-2c which would be classified as a high temperature appliance, not a medium temperature appliance. The requirement for such a hood with 3 sides open is 100 times the area of the hood, not 75 times the area of the hood. Reference Section 507.13.2, IMC 2000.
2. If RTU-1 and RTU-2 are being used to provide makeup air for the exhaust hoods, show the rooftop units are electrically interlocked with the hoods in compliance with Section 508.1, IMC 2000.
3. Provide the listing information for the tortilla machine and its vent or show how the equipment complies with Section 506 and 507, IMC 2000.
08/29/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
09/13/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2004 SUE REEVES OUT TO CUSTOMER Completed
09/16/2004 SUE REEVES REJECT SHELF Completed