Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM02971
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02971
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2004 GERRY KOZIOL WWM REVIEW Approved
07/02/2004 ROBERT SHERRY WATER REVIEW Approved
07/08/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate the scale of the plumbing plan shown on sheet P-1. Reference Section 103.2.3, UPC 1994.
2. Provide a separate vent for the combination waste and vent branch that is greater than 15 feet in length (Near E.8-7). Reference Section 910.3, UPC 1994.
3. Show the locations of additional relief vents for the combination waste and vent system. Reference Section B3, UPC 1994.
4. Provide cleanouts for all directly connected sinks. Reference Section 707.4, UPC 1994.
5. Revise the cleanouts for the floor drains located near F.8-7.6 and E.8-7.6 to comply with Section 707.6, UPC 1994.
6. Revise the trap arms of the floor drain located near G-7.6 and the floor sink located near F.8-7.3 to comply with Section 1002.2, UPC 1994.
7. Revise the one-line gas diagram on sheet P-2 to show the sizes of the branch piping to the appliances.
8. Revise the developed lengths of the low-pressure gas lines to the appliances located on the ground floor as shown on the one-line gas diagram on sheet P-2 to coordinate with the plumbing plan and the roof height. Revise the size of the low-pressure gas line as required. Reference Section 1217.0, UPC 1994.
07/08/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the enclosing shaft for the grease duct (Detail 2/A-7) to provide a minimum separation of 6" between the duct and the shaft. Reference Section 506.3.11, IMC 2000.
2. Provide justification for the exhaust flowrate of Hood T-2c not complying with Section 507.13.2, IMC 2000.
3. Clarify why Note 4 of the Hood Schedule calls for a maximum exhaust velocity that is less than that specified for hood D-8. . Reference Section 106.3.1, IMC 2000.
4. Show how the makeup air for the hoods and oven exhaust complies with Section 508.1, IMC 2000.
5. Show how the tortilla hood and vent complies with Section 506 and 507, IMC 2000.
6. Provide calculations to show that the outside air provided by AC-1 and AC-2 complies with Section 403.3, IMC 2000.
07/15/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Provide a design for the 3 1/2x12 beam shown on trellis plan sheet S-2.
2) Show a detail of hood connections. How many threaded rods connect the
hood to its support. If 2 rods are used for the hood show how the other end
is supported.
3) Show how the 2x6 are attached to the trellis.
07/25/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.sheet E-4 PROVIDE 'BD1' CONDUCTOR AND CONDUIT SIZES. 2. SHEET E-4 KEY NOTE 6 MISSING. INDICATE SIZE OF GROUNDING ELECTRODE CONDUCTOR AT 150 KVA TRANSFORMER. 3. KEY NOTE 2 SHEET E-4(3#1'S,#6 GRD.) TOO SMALLFOR 400 AMP OVERCURRENT PROTECTION.(PLEASE CLARIFY)

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2004 DELMA ROBEY OUT TO CUSTOMER Completed