| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02970 DENIED 6/30/04 1. Size the grounding electrode conductor. 2. Provide the TEP reference for the Available Fault Current of 10,000A, a contact person and telephone number, or TEP's site drawing for this service containing such information. |