Permit Number: T04CM02941
Parcel: 12709012C

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T04CM02941
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02941 DENIED 8/24/04
1. Please ground the transformer as a Separately Derived System per NEC 250.30.
2. Please specify the secondary to the new transformer as not to exceed 10'. Reference NEC 240.21 (C).