Permit Number - T04CM02932
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the indirect waste from the coffee machine, soda machine, and the ice machine, which are routed to the floor sink, comply with the requirements of Section 803.0, UPC 1994.
2. Show where the discharges from the backflow preventers are to be routed.
3. The size and discharge rating of the floor sink shall be based on the fixtures and appliances discharging into it. Reference Sections 702.0, and the footnote to Table 7-3, UPC 1994.
10/15/2004 Doug Williams ENGINEERING REVIEW Denied The Hydrologic and Hydraulic Report meets or exceeds the minimum requirements for approval. The following comments must be addressed prior to approval of this permit:

SITE PLAN:

Depict the limits of the 100-year floodplain, with water surface elevation(s) indicated on sheet T-1.

The Tenant Improvement Plans may not be stamped approved until 2 complete plan sets addressing the comment above, with no penciled revisions, are provided. An over-the-counter Engineering Division review/approval may be coordinated with me at such time.

Please feel free to call me with any questions at 791-5550 ext. 1189 or email at DWillia1@ci.tucson.az.us

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
10/19/2004 Peter McLaughlin ZONING REVIEW Denied TO: Mirek Edward
4229 E. Seneca Street
Tucson, AZ 85712
FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM02932
Remodel Texaco Service Station to retail sales building
4701 E. 29th Street
Site Plan Review (2nd review)

TRANSMITTAL: October 20, 2004


Upon completion of the following revisions/additions, an over the counter review may be arranged to obtain stamped approval by the zoning review section without resubmitting the site plan. The following item must be revised on or added to the site plan:

1. Because the existing paved area is being re-striped to accommodate new parking, a yellow colored site card must be obtained from the DSD permit clerks for site plan review.
DS 2-02

2. Add a calculation of handicapped parking required (1 h/c space) and provided (1 h/c space).
DS 2-02.2.2.A.4
ANS/ IBC

3. On the site plan to be stamped approved all revisions and details must be ink rather than in pencil.

4. Add the development designator under the zoning information. The development designator for the retail sales use in the C-2 zone is "31". LUC 2.5.4.2.B.2

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2004 LISA LESNY OUT TO CUSTOMER Completed
10/21/2004 SUE REEVES REJECT SHELF Completed