08/18/2004 Jim Egan FIRE REVIEW Approved
08/18/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the electrical data for the heat pumps to coordinate with the added heating capacity. Clarify the power being supplied to the heat pumps: the equipment model number indicates 208/230-3-60 but 230-1-60 is specified. Coordinate with the electrical drawings.
08/18/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the sizes of the vents in the waste and vent schematic. Reference Sections 311.5, 703.2, and 904.1, UPC 1994.
2. Finish labeling the pipe sizes on the waste and vent schematic, especially the wet vent. Reference Section 103.2.3, UPC 1994.
3. Verify that the existing water heater is equipped with a listed expansion tank. Reference Section 608.3, UPC 1994.
08/20/2004 Gerry Koziol WWM REVIEW Approved
09/02/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
09/16/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Approv-Cond