| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2004 | Jim Egan | FIRE | REVIEW | Approved | |
| 08/18/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the electrical data for the heat pumps to coordinate with the added heating capacity. Clarify the power being supplied to the heat pumps: the equipment model number indicates 208/230-3-60 but 230-1-60 is specified. Coordinate with the electrical drawings. |
| 08/18/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the sizes of the vents in the waste and vent schematic. Reference Sections 311.5, 703.2, and 904.1, UPC 1994. 2. Finish labeling the pipe sizes on the waste and vent schematic, especially the wet vent. Reference Section 103.2.3, UPC 1994. 3. Verify that the existing water heater is equipped with a listed expansion tank. Reference Section 608.3, UPC 1994. |
| 08/20/2004 | Gerry Koziol | WWM | REVIEW | Approved | |
| 09/02/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/16/2004 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Approv-Cond |