Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM02922
Parcel: 11601004B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2004 Jim Egan FIRE REVIEW Denied Minimum of two exits required. Exit through storage room not permitted. (See 2000 IBC/IFC Section 1004.2.3)
06/25/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation based on Sections 403.3 and 403.3.2, IMC 2000.
2. Show how the building pressurization is to be accommodated. Reference Section 403.1, IMC 2000.
3. Revise note 4/M1.1 to coordinate with the mechanical floor plan.
4. Provide smoke detectors in the return air ducts, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC.
5. Show how the specified heat pumps are capable of maintaining a minimum temperature of 68°F in the interior spaces intended for occupancy on a design heating day (32°F). Reference Section 309.1, IMC 2000.
06/25/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for mercantile occupancy.
3. Provide complete plumbing plan, including waste and vent isometrics. Reference Section 103.2.3, UPC 1994.
06/25/2004 ROBERT SHERRY WATER REVIEW Approved
06/29/2004 GERRY KOZIOL WWM REVIEW Denied need waste water plumbing drawings
07/08/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM02922 .. 2211 W. IRONWOOD HILL DRIVE .. DGL .. FIRST REVIEW COMMENTS ..
.. #1 THROUGH #16 .. 7/15/04 ..

S1. Provide completed Code Review Checklist , per International Building Code.

S2. Provide drawings using International Building Code designations and references vs Uniform Building Code , ref Cover Sheet and SP-1.

S3. Provide structural calculations addressing new equipment mounted on the roof , show capacity of supports are not overstressed , ref drawing M1.1.

S4. Clarify details 5/A3.2 and 6/A3.2 , as existing structure is wood roof trusses w/ plywood sheathing , revise or explain metal decking and concrete.

S5. Provide complete architectural and structural design and details for parapet extension , ref drawing SP-1 and S2.1.

S6. Separate Permit required for signs.

S7. Separate Building Permit required for storage racks over 8 feet high.

S8. Existing building shear walls use 5/8" gypsum board per prior Structural Engineer's Design vs use of plywood sheathing specified by the Structural Engineer for this Project , please explain and provide revised calculations and design for the front elevation.

S9. Justify soil bearing pressure as prior design is for 1000 psf per calculations by prior Engineer vs 1500 psf by the Engineer of this Project.

S10. Clarify protection for exposed steel , including parapet bracing per IBC Section 2203.2.

S11. Clarify how splices are made , to maintain building continuity over new and existing openings.

S12. Coordinate architectural and structural at window walls , ref 2/SP-1 , structural column locations on S2.1.

S13. Provide design and details for one-hour fire-rated exit corridor through storage at 2nd exit , per IBC Chapter 10, 11, and 34.

S14. Fully dimension and detail accessible toilet rooms per IBC Chapter 11 , 34 and ANSI A117.1 - 1998ed , including access to toilet rooms .

S15. Provide structural calculations and details for wing wall support details 1/A3.1 , 2/A3.1 , 3/A3.1 , 4/A3.1 and drawing A1.1.

S16. Special Inspection required for :
1. Epoxy anchors
2. Field Welding
3. Shop welding


Questions? Call Douglas Laakso, Structural Plans Examiner COT- DSD,
At (520) 791-5550 x 1111.
07/22/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Minimum font size for City of Tucson is #10, which is just over 1/8". Please correct on Sheets E0.2, E1.1, and any other sheet for which this applies.
2. Regarding Note 19 on Sheet E0.1, the City of Tucson enforces 2000 IBC. Please correct from 1997 UBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2004 BETH GRANT OUT TO CUSTOMER Completed
08/17/2004 SUE REEVES REJECT SHELF Completed