| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/24/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/24/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/24/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/28/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02913 DENIED 6/24/04 1. Provide overload protection for the 3/4 HP Ice Cream Churn Motors, or justify otherwise. 2. Panel load calculations were checked applying the demand of 125% on Circuits 11, 13, 15, and 17 as continuous load that was not accounted for on the schedule. Demand factors for kitchen equipment were applied per NEC Table 220-20. Resultant values were higher than indicated on plans. Please re-evaluate panel load calculations. 3. Please specify rating of panel in amps, and note whether it has a main or is MLO. |
| 06/29/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/29/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/29/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/29/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/29/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |