Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM02913
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/24/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
06/24/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
06/24/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/24/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/28/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02913 DENIED 6/24/04 1. Provide overload protection for the 3/4 HP Ice Cream Churn Motors, or justify otherwise. 2. Panel load calculations were checked applying the demand of 125% on Circuits 11, 13, 15, and 17 as continuous load that was not accounted for on the schedule. Demand factors for kitchen equipment were applied per NEC Table 220-20. Resultant values were higher than indicated on plans. Please re-evaluate panel load calculations. 3. Please specify rating of panel in amps, and note whether it has a main or is MLO. |
06/29/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
06/29/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
06/29/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/29/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/29/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |