06/24/2004 JIM EGAN FIRE REVIEW Approved
06/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/24/2004 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
06/24/2004 ROBERT SHERRY WATER REVIEW Approved
06/28/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02913 DENIED 6/24/04
1. Provide overload protection for the 3/4 HP Ice Cream Churn Motors, or justify otherwise.
2. Panel load calculations were checked applying the demand of 125% on Circuits 11, 13, 15, and 17 as continuous load that was not accounted for on the schedule. Demand factors for kitchen equipment were applied per NEC Table 220-20. Resultant values were higher than indicated on plans. Please re-evaluate panel load calculations.
3. Please specify rating of panel in amps, and note whether it has a main or is MLO.
06/29/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/29/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
06/29/2004 GERRY KOZIOL WWM REVIEW Approved
06/29/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved