Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM02890
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2004 | MELISSA POULIN | WWM | REVIEW | Denied | Need to show location/method of connection to public sewer. |
| 08/17/2004 | David Witt | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T04CM02890 8/18/04 730 E. LESTER ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. STRUCTURAL PLANS: 1. PLEASE PROVIDE A LISTING FOR THE " 16" PRO 150 " TJI OVER THE ENTRY CLOSET. 2. JUSTIFY THE 2 - 15" PRO 550 ABILITY TO ACCOMMODATE THE SECOND STORY BRACED WALL PANELS. 3. PROVIDE A FOOTING FOR THE PORCH (100) STORAGE BEARING WALL OR EXTEND THE BEAM TO BEAR ON THE LIVING ROOM WALL AND CHECK THE BEAM FOR THE INCREASED SPAN. 4. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. 5. DETAIL GABLE END BRACING CONNECTIONS. ELEVATIONS: 1. FOAM INSULATION: CLARIFY YOUR COMPLIANCE WITH R318 ON THE MAIN WALLS AND THOSE WALLS TO THE ATTIC PER R318.2.3. SECTIONS - DETAILS - MISC. NOTES: 1. 1, etc. / A7 ; PLEASE SPECIFY THE ANCHOR BOLT LENGTH OR LENGTH OF PENETRATION INTO THE CONCRETE. 2. 1 / A3 ; PROVIDE THE SIZE OF THE LEADER. 3. 4 / A7 ; THE SIMPSON "PB" SERIES DOESN'T ELEVATE THE POST 1" ABOVE THE SLAB. HOW IS IT ELEVATED? 4. 7,9 / A7 ; THE NAILING OF THE PLATE CONFLICTS WITH TABLE R602.3(1). PLEASE JUSTIFY. 5. 10 / A7 ; PLEASE SPECIFY THE JOIST HANGER. 6. 11 / A7 ; 16d NAILS ARE TO SHORT TO NAIL A 3X LEDGER. 7. 14 / A7 ; THE WALL APPEARS TO BE SUPPORTED BY ONE 2X8 WHICH CONFLICTS WITH THE FRAMING PLAN AND IS INADEQUATE. 8. 15 / A7 ; PROVIDE THE NAIL PATTERN FOR THE BLOCKS TO THE ROOF SHEATHING AND TO THE PLATE. 9. 17 / A7 ; THE FIRE BLOCK SHOULD BE AT THE CEILING LINE. 10. 10 / A7 ; PLEASE PROVIDE THE NAIL PLATE FOR THE SINGLE TOP PLATE SPLICE. SEE R602.3.2 . 11. 2 / A7 ; JUSTIFY THE 32" PIN SPACEING. 12. STAIR AT MID LANDING / A7 ; JUSTIFY THE 2 - 16d FOR A THE LEDGER TO STUD CONNECTION. 13. STAIR AT LANDING / A7 ; THE MAXIMUM TREAD HEIGHT IS 7.75" OVERALL, TREAD TO TREAD. DOES THE 7.75" NOTE REFER TO THE BLOCK OR THE OVERALL HEIGHT? 14..PLEASE DESCRIBE THE STAIR STRINGER CONNECTION AT THE TOP AND AT THE BOTTOM. 15. WINDOW SCHEDULE / A2 ; "W-2 " IS ILLUSTRATED AS 2'-8" WIDE BUT CALLED OUT AS 4'-8" WIDE. PLEASE CO-ORDINATE. 16. HEADER SCHEDULE / A6 ; JUSTIFY THE "H-2" HEADER FOR THE W-3, W-4 AND THE D-13 OPENINGS. PLUMBING PLANS: 1. PLEASE CLARIFY THE ISOMETRIC WASTE AND VENT LINES. PLEASE ELIMINATE THE FLAT VENTS AND ILLUSTRATE THE TRAPS AS BEING ABOVE THE HORIZONTAL DRAINS. LARGER SCALE, PLEASE. 2. PLUMBING FIXTURE SACHEDULE / A9 ; THE HOSE BIBS SHOULD BE 3 f.u. EACH. 3. PLEASE CHECK THE DESIGN LENGTH OF THE WATER DISTRIBUTION LINES. IT SCALES 120' TO THE SIDE OF THE HOUSE WITHOUT TURNING IN AND RISING TO THE SHOWER HEAD ON THE UPPER FLOOR. 4. PLEASE JUSTIFY THE ½" SUPPLIES TO THE CLOTHES WASHER. SEE UPC TABLE 6-4 OR APPENDIX A . 5. PLUMBING NOTE 4 / A9 ; INDICATE THE LOCATION, ON THE PLAN, OF THE MANIFOLD. 6. PLUMBING NOTE 16 / A9 ; PLEASE INDICATE THE P AND T VALVE IS TO BE SET FOR 150#. SEE UPC 608.4. IF THE PRESSURE IS SET LOWER THAN THE SUPPLY PRESSURE THE VALVE WILL STAY OPEN. PROVIDE AN EXPANSION TANK. MECHANICAL PLANS: 1. MECHANICAL NOTE 13 / A8 ; THE CONDENSATE LINE IS TO BE IN ACCORD WITH THE STATE PLUMBING CODE. 2. THE LOCATION OF THE 19 X 11 SUPPLY RIGID DUCT UP DOESN'T CO-INCIDE WITH THE LAY OUT UPSTAIRS. FURR-DOWN? HOW DOES THE "19 X 11" COMPLY WITH M1603 ? ELECTRICAL PLANS: 1. PROVIDE A RECEPTACLE ON THE EAST WALL OF THE DINING AREA. 2. PROVIDE RECEPTACLES BETWEEN THE CLOSET DOORS AND THE BEDROOM DOORS IN BEDROOMS 2 AND 3 . 3. PLEASE PROVIDE A RECEPTACLE IN THE UPPER FLOOF HALL. 4. PLEASE LOCATE THE SMOKE DETECTORS AT THE UPPER END OF THE SCISSOR TRUSSES. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. THE ENERGY CODE LISTS 2100 HEATING DEGREE DAYS FOR TUCSON. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 08/19/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |