Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM02866
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02866
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2004 DAN CASTRO ZONING REVIEW Approved
07/14/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
07/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/14/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/07/2004 GERRY KOZIOL WWM REVIEW Approved