Permit Number: T04CM02866
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02866
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2004 JIM EGAN FIRE REVIEW Approved
06/22/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
06/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM02866 DENIED 6/22/04
1. Plans shall be prepared and sealed by a Registrant in the State of Arizona.
2. Plans shall comply with NEC 2002. For example, it appears that case lighting circuits should count 1.4 VA, not .72, and account for continuous load.
06/28/2004 TACHONG1 PLUMBING-COMMERCIAL REVIEW Needs Review
06/28/2004 TACHONG1 ZONING REVIEW Needs Review
06/28/2004 TACHONG1 WWM REVIEW Needs Review
06/28/2004 TACHONG1 ENGINEERING REVIEW Needs Review
06/28/2004 TACHONG1 MECHANICAL-COMMERCIAL REVIEW Needs Review
06/28/2004 TACHONG1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2004 TAMI ACHONG OUT TO CUSTOMER Completed