Permit Number: T04CM02854
Parcel: 126170510

Address:
525 S IRVING AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM02854
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2004 GERRY KOZIOL WWM REVIEW Approved
07/08/2004 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM02854
07/13/2004 525 S. Irving Ave.

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2000 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. All plans shall be legible and a scale no smaller than ¼ inch = 1-foot shall be used for all floor plans, framing plans and elevations. Details and cross sections shall be a minimum 3/8 inch = 1-foot scale.
2. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
3. List the square footage for all the following areas separately on the drawings:
- Livable area
- garage
- porch / patio covers
- decks
4. All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.
FOUNDATION PLANS:
1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1, a soils report is not required. It is up to the designer / homebuilder to be aware of the soil and conditions of the site. If soil testing has been done, a copy of the soils report shall be submitted with the construction plans, and the foundation design shall reflect the soils reports recommendations.
1. All foundation hold-downs and anchor-bolt spacing for brace walls shall be specified and located. Two hold-downs specified designate where each type will be used.
FLOOR PLANS:
1. Provide ½" gypsum board on all walls common to the garage and house in compliance with R309.2. Where separation is a floor-ceiling assembly, the structure supporting the separation shall also be protected by a minimum ½" gypsum board or equivalent per R309.2.
STRUCTURAL PLANS:
1. 2x4 or 2x6 exterior wall framing? Interior wall framing ?
ELEVATIONS:
1. If venting roof then detail for insulation at top of roof framing would be inappropriate. Clarify if you want to have no-vent roof framing with insulation at top or vented roof framing with insulation at bottom of roof framing / above ceiling.?
MECHANICAL PLANS:
1. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements. Detail how you will comply. Combustion Air must be provided from outside air for new construction.
ELECTRICAL PLANS:
1. Receptacle outlets shall be provided at each kitchen counter space wider than 12", and shall be installed so that no point along the wall line is more than 24" from a receptacle outlet, per E3801.4.1. Above dishwasher?
2. Island or peninsula counter tops shall have at least one receptacle outlet at each counter space with a long dimension of 24" or greater, and a short dimension of 12" or greater, per E3801.4.2 and E3802.4.3. May be mounted no more than 12" below counter if max. 6" counter overhang at kitchen sink peninsula.
3. All receptacle outlets in bathrooms, kitchens, unfinished basements, garages or carports, at grade level and within 6' of a wet bar or kitchen sink shall have ground fault circuit interrupting protection. Note on the drawings at each outlet requiring such protection, per E3802.
4. Submit panel schedule showing wire size circuit 1,3 and 5,7.
MODEL ENERGY CODE:
NOTE: If addition is < 20% of total square footage of dwelling, you are not required to meet MEC requirements.
1. Provide energy calculations per the 1998 IECC and comply with IRC chapter 11.
2. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided.
If you have any questions, please contact your assigned plans examiner Christy Foreman at 791-5550, extension 1113.