Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM02814
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2004 | Gerry Koziol | WWM | REVIEW | Approved | |
| 11/09/2004 | Terry Stevens | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS for Activity # T04CM02814 11/10/2004 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: 1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. FOUNDATION PLANS: 1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1, a soils report is not required. It is up to the designer / homebuilder to be aware of the soil and conditions of the site. If soil testing has been done, a copy of the soils report shall be submitted with the construction plans, and the foundation design shall reflect the soils reports recommendations. 2. Dimension the depth into undisturbed soil for each footing type and condition per IRC table R403.1. Detail 9/A5 missing above requirement. 3. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with 7" embedment into concrete or masonry. Maximum spacing 6' O.C. and within 12" of each end of sill plate per R403.1.6.----Detail 9/A5 ----8"AB not long enough 4. Specify all post anchors on the foundation plan.-------Detail 10/A5 call out post base not just simpson post base. FLOOR PLANS: 1. Locate and identify brace wall types and locations along with the appropriate nailing schedule. 2. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height. STRUCTURAL PLANS: 1. Completely detail all connections and cross-reference to the foundation and framing plans: Beam to post-----Detail 4/A5 min. 6" into post for lag Ledgers to framing-------provide positive connection, H2.5, A35, or both at bearing and nonbearing walls Indicate required fire blocking 2. Lintel schedule and detail have different size angles.----------clarify 3. Provide crickets and scuppers for new roof. 4. New window at old kitchen location shows a 2x header, not allowed in adobe wall. 5. Provide special inspection for epoxy bolts-------detail 13/A5 ELEVATIONS: 1. Note and specify all roof slopes appropriate to material. (minimum allowable roof slope is ¼" per foot per R905.11.1) 2. Note and size all roof drains or scuppers on flat roofed areas per R903.4. 3. New roof drain at existing structure requires an overflow drain that is independent from the roof drain. Inlet must be min. 2" above the lowest point of the roof. 4. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply. PLUMBING PLANS: 1. Gas: Indicate size of existing gas lines. 2. Provide pressure and temperature relief valve at water heater. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down. ELECTRICAL PLANS: 1. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6. 2. Show locations of smoke detectors per R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. MODEL ENERGY CODE: 1. NOTE: If addition is < 20% of total square footage of dwelling, you are not required to meet MEC requirements. 2. Provide energy calculations per the 1998 IECC and comply with IRC chapter 11. 3. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided. If you have any questions, please contact your assigned plans examiner Terry Stevens at 791-5550, extension 1112. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 11/16/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |