Permit Number: T04CM02796
Parcel: 10510079B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02796
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise detail 1/M2 to conform to the requirements of Section 506.3.8, IMC 2000. Provide an approved drain outlet at the bottom of the fan scroll leading to an approved grease reservoir.
10/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets of the icemaker for determination. Reference Section 603.0, UPC 1994.
2. Revise the termination shown for the WH-1 vent to comply with the requirements of Section 517.3, UPC 1994.
10/25/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
11/08/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Approved CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/9/04
ACTIVITY NUMBER: T04CM02796
PROJECT NAME: NEW RESTAURANT / LOFT
PROJECT ADDRESS: 427 E. LIMBERLOST
ARCHITECT / ENGINEER: STEPHEN MOSS
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1. Clarify location of bldg. On site plan and dimension distances from existing buildings and property lines. Information necessary for code analysis Table 602 and Table 704.8. - Per location of building table 602 type VA construction requires 1 hr. wall - east wall. Clarify / justify including roof overhang per section 704- 704.11.

2. Further clarification of exit stairwell see section 1005.3.6.5 exterior stairway protection. This stairwell meets exception (1) therefore stair separation from interior of bldg. @ R-3 is not required. Therefore walls of stairwell are not required to be a firewall.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2004 TAMI ACHONG OUT TO CUSTOMER Completed
11/10/2004 SUE REEVES REJECT SHELF Completed