Permit Number: T04CM02775
Parcel: 11306129E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM02775
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2004 JIM EGAN FIRE REVIEW Approved
06/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/17/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
06/17/2004 ROBERT SHERRY WATER REVIEW Approved
06/17/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
06/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/17/2004 JIM TATE ENGINEERING REVIEW Approved
06/18/2004 GERRY KOZIOL WWM REVIEW Approved
06/18/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM02775 DENIED 6/17/04
1. Account for 25% of largest motor on panel schedule per NEC 430-24.
2. Phases A & C are overloaded on the panel schedule at 226A and 203A respectively.
3. Pls clarify whether Panel LB and its feeder are to be new or existing. Both are indicated on Line Diagram, and they can not be both new and existing.