| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 06/17/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/17/2004 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/17/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/17/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 06/17/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 06/17/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 06/18/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/18/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM02775 DENIED 6/17/04 1. Account for 25% of largest motor on panel schedule per NEC 430-24. 2. Phases A & C are overloaded on the panel schedule at 226A and 203A respectively. 3. Pls clarify whether Panel LB and its feeder are to be new or existing. Both are indicated on Line Diagram, and they can not be both new and existing. |