Permit Number: T04CM02743
Parcel: 110082670

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T04CM02743
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2004 GERRY KOZIOL WWM REVIEW Approved
06/30/2004 PAUL MACHADO ENGINEERING REVIEW Approved
07/23/2004 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project #T04CM02743

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen and pencil corrections on final prints will not be acceptable. To avoid delays ensure all corrections have been made, are complete and have been coordinated on all applicable details and notes.

Floor Plan

1. If exterior door to bedroom #2 is new them provide notes for construction.
2. Window adjacent exterior bedroom door is required to be tempered.
3. Provide window size and the operable portion of that window for bathroom in bedroom #2.
4. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front of not less than 21" per R307.2.
5. Note that bathtub and shower enclosures shall be finished with ceramic tile or a listed enclosure, to a height or 72" above the drain per R702.4 and R307.2.
6. Note and specify that shower enclosures shall have a minimum finished interior of 1024 sq. inches and shall be capable of encompassing a minimum 30" circle per UPC sec 410.

Plumbing and Mechanical Plan

1. Provide note if gas line is new or existing. If new provide Btu demand for each unit and total developed length of pipe.
2. Provide note of combustion relief and P&T line for water heater. Existing or new?
3. Note on plans: Mechanical shall comply with chapters 12-16 and 18-24 2000 IRC.
4. Size all dirty arms.
5. Provide cleanout at kitchen sink.
6. Note type of waste pipe.
7. Provide fixture unit calculation for entire house per table 6-3 1994 UPC. Provide pipe size from water meter to house sized per table 6-4 1994 UPC.
8. Note on plans compliance with water conservation; Water closets 1.6 gallons per flush. Sinks and showerheads 3 gallons per minute.
9. Note on plans that shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
10. The city of Tucson has not adopted the plumbing section of the IRC 2000. The current code being used is the 1994 UPC with state amendments. All plans must reference this code.

ANY QUESTIONS PLEASE CONTACT NEIL SAUNDERS @791-5550 x1113