Permit Number: T04CM02705
Parcel: 110092760

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM02705
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2004 GERRY KOZIOL WWM REVIEW Approved
07/06/2004 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T04CM02705

7/8/04 3066 N. WILLOW CREEK DR.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FLOOR PLANS:

1. SHEAR WALL SCHEDULE / A-2 ; PLEASE IDENTIFY SW-2 .

2. SHEAR WALL SCHEDULE / A-2 ; HOW DO THE SHEAR WALL ANCHOR BOLT LOCATIONS COMPLY WITH R602.10.6 ?

3. DOOR NOTE #3 / A-2 ; THESE DOORS SOUND LIKE DOORS TO A POOL AREA. THE DOOR ALARM ISN'T PERMITTED IN TUCSON. IF THERE'S A POOL, PLEASE SHOW IT ON THE SITE PLAN. WHERE ARE THESE DOORS LOCATED?

ELEVATIONS:

1. NORTH AND EAST ELEVATION / A-4 ; PLEASE CHECK THE NET COMBUSTION AIR SIZE USING TABLE A OF THE STATE REVISIONS TO THE U.P.C. THE REVISIONS ARE ON OUR WEB SITE.

2. 4 / A-4 ; THE WEST ELEVATION APPEARS TO BE A CROSS SECTION. PLEASE INDICATE IT'S LOCATION ON THE FLOOR PLAN.

SECTIONS - DETAILS - MISC. NOTES:

1. HOW DOES THE GWB ON THE CEILING FRAMED @ 24" O.C. COMPLY WITH TABLE R702.3.5 FOOTNOTE D ?

2. 4 / A-5 , NOTE 7 ; JUSTIFY THE ½" SPACE BETWEEN THE PANELS.

3. 7 , 12 / A-3 ; PLEASE JUSTIFY THE LEDGER / STUD CONNECTION.

4. 7 , 12 / A-3 ; THE ITT3514 DON'T APPEAR TO FIT THE T.J.I.s SPECIFIED.







PLUMBING PLANS:

1. PROVIDE THE INPUT DEMAND OF THE EXISTING GAS APPLIANCES. IS THE GAS LINE BETWEEN THE GAS METER AND THE ADDITION'S "T" ADEQUATE TO SUPPLY THE EXISTING AND THE PROPOSED GAS DEMAND?

2. PLUMBING FIXTURE CONNECTION SCHEDULE / MP-1 ; PLEASE USE THE U.P.C. FOR THE F.U. VALUES.

3. 6 / MP-1 ; THE P & T LINE IS NOT PERMITTED TO GO UPHILL.

4. PLUMBING NOTE 8 / MP-1 ; THE U.P.C. SHOULD BE THE CODE REFERENCE.

5. PLUMBING NOTE 8 / MP-1 ; WHEN THE GRADE OF A WASTE PIPE DROPS TO 1%, IT'S REQUIRED TO BE NOT LESS THAN 4" . SEE UPC 708.

6. IF THE WATER SUPPLY TO WATER HEATER 2 IS SUPPLIED THROUGH THE EXISTING WATER DISTRIBUTION SYSTEM, JUSTIFY IT'S ABILITY TO SUPPLY THE EXISTING AND THE PROPOSED F.U.s .


MECHANICAL PLANS:

1. MECHANICAL NOTE 1 / MP-1 ; THE IRC AMENDMENTS SHOULD BE THE CITY OF TUCSON'S AMENDMENTS.

2. PLEASE CHECK THE COMBUSTION AIR NET SIZE IN THE STORAGE ROOM DOORS. SEE TABLE A OF THE STATE AMENDMENTS TO THE UPC.

3. PLEASE CHECK THE SUPPLY AIR AND THE RETURN AIR SIZES IN ACCORD WITH M1602 AND M1603.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.

2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS
AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2004 TAMI ACHONG OUT TO CUSTOMER Completed
07/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed