Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02694
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/24/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans (e.g. call out the R-value for the roof insulation) and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000. |
| 11/24/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the sizes of the branch water pipes to P-4 and the section of CW pipe serving the water heater and P-4 to correspond to the provided calculations. Reference Appendix A, UPC 1994. |
| 11/24/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Comments 1 and 2 have yet to be satisfied. Your response letter dated 11 September 04, shows that required waterclosets is 36, the number provided as shown is 34. two short. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/29/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 11/29/2004 | SUE REEVES | REJECT SHELF | Completed |