Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02692
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000. 2. Comment not addressed. Indicate the minimum amount of outside air to be provided by the HVAC system and the amount of outside air to be delivered when the facility is fully occupied. Provide a sequence of operation to show how the CO2 sensors are to be used to control the amount of outside air delivered to the space. Reference Sections 403.3 and 405.1, IMC 2000. 3. Clarify the design of the exhaust system with respect to the number of inlets. Reference Section 106.3.1, IMC 2000. |
10/05/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide the sizes of the scuppers shown on the plans. Provide overflow protection for the roof. Reference Appendix D, UPC 1994. 2. Correct the arithmetic in the provided water calculations and use the minimum available water pressure as the design pressure. Revise the sizes of the branch water pipes as required. Reference Appendix A 1.1, UPC 1994. 3. The routes and size of the existing water lines as shown of sheet 0.2 do not clearly show how the proposed building is to be provided with water. The size and location of the water meter and RPBP are not shown on sheet 0.2. Reference Section 610.0, UPC 1994. |
10/11/2004 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/14/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
10/14/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |