Permit Number: T04CM02691
Parcel: 124120620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02691
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000.
2. The provided sequence of operation for the CO2 sensors (sheet 15.1) indicates that the maximum amount of outside air to be provided by the HVAC system when the facility is fully occupied is only 50% of the required amount of outside air. Revise the controls to provide the required amount of outside air to the space. Reference Section 405.1, IMC 2000.
3. Clarify the design of the exhaust system with respect to the number of inlets. Reference Section 106.3.1, IMC 2000.
10/05/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the materials of construction for the existing 6" sewer. If the existing sewer is not made of materials approved for use under or in a building, show how the sewer is to be relocated. Reference Section 313.4, UPC 1994.
2. Comment not addressed on the architectural drawings. Provide the sizes of the scuppers shown on the plans. Provide overflow protection for the roof. Reference Appendix D, UPC 1994.
3. The provided water calculations indicate that the branch water piping in the building has been undersized. Reference Section 610.5, UPC 1994.
10/14/2004 Gerry Koziol WWM REVIEW Denied NEED TO CLARIFY LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER.
10/21/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/25/2004 SUE REEVES REJECT SHELF Completed