Permit Number: T04CM02691
Parcel: 124120620

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM02691
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/6/04
ACTIVITY NUMBER: T04CM02691
PROJECT NAME: ACTIVITY BLDG. MILES EXPLORATORY SCHOOL
PROJECT ADDRESS: 1400 E. BROADWAY BLVD.
ARCHITECT / ENGINEER: CDG ARCHITECTS
PROJECT REVIEWER: CHRISTY FOREMAN
PHONE: 7901-5550 X1108
EMAIL: CFOREMA1@CI.TUCSON.AZ.US

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1. Provide water closet stall for men's restroom, therefore allow both fixtures to be used with privacy.
2. 3 water closets required for women's restroom per code table 2902.1.
3. Clarify landing into bldg. - grade change? Clarify note 9 site plan / parking plan sht. 1.1.
4. Sht. 16.1 exit light over window instead of door.
08/04/2004 ROBERT SHERRY WATER REVIEW Approved
08/04/2004 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000.
2. Indicate the minimum amount of outside air to be provided by the HVAC system and the amount of outside air to be delivered when the facility is fully occupied. Provide a sequence of operation to show how the CO2 sensors are to be used to control the amount of outside air delivered to the space. Reference Sections 403.3 and 405.1, IMC 2000.
3. Clarify the design of the exhaust system with respect to the number of inlets and the sequence of operation. Reference Section 106.3.1, IMC 2000.
08/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the existing 6" sewer is to be relocated or otherwise accommodated with the proposed building that is being built directly over it. Reference Section 313.0, UPC 1994.
2. Provide the sizes of the scuppers shown on the plans. Provide overflow protection for the roof. Reference Appendix D, UPC 1994.
3. Revise the waste units for the mop basin in the fixture schedule (a 3" waste has 6 waste fixture units). Reference Table 7-3, UPC 1994.
4. Show the size and route of the water line serving the proposed building along with the size and location of the water meter and RPBP. Reference Section 610.0, UPC 1994.
5. Provide calculations to show how the water piping has been sized. Reference Section 610.5, UPC 1994.
6. Confirm that the wall-mounted water heater complies with the access requirements of Section 511.0, UPC 1994 with AZ State amendments.
7. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
08/09/2004 Gerry Koziol WWM REVIEW Denied NEED TO CLARIFY LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER.
08/15/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2004 DHERRON1 OUT TO CUSTOMER Completed
08/17/2004 SUE REEVES REJECT SHELF Completed