Permit Number: T04CM02690
Parcel: 116262060

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02690
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000.
2. The provided sequence of operation for the CO2 sensors (sheet 15.1) indicates that the maximum amount of outside air to be provided by the HVAC system when the facility is fully occupied is only 50% of the required amount of outside air. Revise the controls to provide the required amount of outside air to the space. Reference Section 405.1, IMC 2000.
3. Clarify the design of the exhaust system with respect to the number of inlets. Reference Section 106.3.1, IMC 2000.
10/06/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed on the architectural drawings. Provide the sizes of the scuppers shown on the plans. Provide overflow protection for the roof. Reference Appendix D, UPC 1994.
2. The routes and size of the existing water lines as shown of sheet 1.1 do not clearly show how the proposed building is to be provided with water. The size and location of the water meter and RPBP are not shown on sheet 1.1. Reference Section 610.0, UPC 1994.
3. Correct the arithmetic in the provided water calculations and use the minimum available water pressure as the design pressure. Revise the sizes of the branch water pipes as required. Reference Appendix A 1.1, UPC 1994.
10/08/2004 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/03/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2004 BETH GRANT OUT TO CUSTOMER Completed
11/18/2004 SUE REEVES REJECT SHELF Completed