Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T04CM02683
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Specify the size of base plate for the middle column. 2) Show the itemized loading at the floor level. 3) What is the LIVE LOAD for the floor? 4) Clarify, is steel beam continuous? If so design as such. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 11/07/2005 | GBONILL1 | REJECT SHELF | Completed |