Permit Number: T04CM02683
Parcel: 11714091A

Address:
420 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02683
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a detail to show how the secondary condensate drain is to function. Keynote 12 on sheet M-P1.3 calls for "…3/4" secondary CD from fan coil, no trap and open tee". If the secondary condensate drain is attached to the drain pan of the fan coil, how does it comply with Section 307.2.4, IMC 2000 if it doesn't have a trap?
09/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Revise detail 4/D-P1.6 to coordinate with the riser diagrams (no floor drains are shown on the riser diagrams). Reference Section 103.2.3, UPC 1994.
2. Comment not addressed. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (drain lines serving sinks require cleanouts regardless of length) on the upper floors. Reference Section 707.4, UPC 1994 with State of Arizona amendments.
3. Comment not addressed. Provide suds relief for stacks containing suds-producing fixtures. Reference Section 711.0, UPC 1994. Note: the stacks for P3 and P5 in 2103 and 2104 are 3 stories in height.
4. Comment not addressed. Include the separate dishwasher connection in the fixture unit calculations.
09/23/2004 Gerry Koziol WWM REVIEW Denied Needs 8th floor credit evaluation.
09/28/2004 BLANCA ESPINO ENGINEERING REVIEW Denied 1. Sie Plan approval required.
10/11/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Approved
10/12/2004 DAN CASTRO ZONING REVIEW Denied Structural plans must be approved by Building Review and site plan must be approved by all sections prior to Zoning approval of structural plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed