Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02683
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise detail 4/D-P1.6 to coordinate with the riser diagrams (no floor drains are shown on the riser diagrams). Reference Section 103.2.3, UPC 1994. 2. Comment not addressed. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (drain lines serving sinks require cleanouts regardless of length) on the upper floors. Reference Section 707.4, UPC 1994 with State of Arizona amendments. 3. Comment not addressed. Provide suds relief for stacks containing suds-producing fixtures. Reference Section 711.0, UPC 1994. Note: the stacks for P3 and P5 in 2103 and 2104 are 3 stories in height. 4. Comment not addressed. Include the separate dishwasher connection in the fixture unit calculations. |
09/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a detail to show how the secondary condensate drain is to function. Keynote 12 on sheet M-P1.3 calls for "…3/4" secondary CD from fan coil, no trap and open tee". If the secondary condensate drain is attached to the drain pan of the fan coil, how does it comply with Section 307.2.4, IMC 2000 if it doesn't have a trap? |
09/23/2004 | Gerry Koziol | WWM | REVIEW | Denied | Needs 8th floor credit evaluation. |
09/28/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | 1. Sie Plan approval required. |
10/11/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/12/2004 | DAN CASTRO | ZONING | REVIEW | Denied | Structural plans must be approved by Building Review and site plan must be approved by all sections prior to Zoning approval of structural plans. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/13/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
10/13/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |