Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02682
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the fixture schedule to include the floor drains. Reference Section 103.2.3, UPC 1994. 2. Indirect waste receptors shall not be installed in a cabinet or cupboard. Removing the kick plates and cabinet floors does not make the indirect waste receptors readily accessible. Reference Section 804.1, UPC 1994. 3. Comment not addressed. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (drain lines serving sinks require cleanouts regardless of length) on the upper floor. Reference Section 707.4, UPC 1994 with State of Arizona amendments. Note: see Section 909.0, UPC 1994 for the island venting. 4. Comment not addressed. Include the separate dishwasher connection in the fixture unit calculations. |
| 09/22/2004 | JIM TATE | ENGINEERING | REVIEW | Denied | A copy of the stamped approved Site Plan must be included in the submittal. |
| 09/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a detail to show how the secondary condensate drain is to function. Keynote 12 on sheet M-P1.3 calls for " 3/4" secondary CD from fan coil, no trap and open tee". If the secondary condensate drain is attached to the drain pan of the fan coil, how does it comply with Section 307.2.4, IMC 2000 if it doesn't have a trap? |
| 09/23/2004 | Gerry Koziol | WWM | REVIEW | Denied | NEED TO SHOW LOCATION/METHOD OF NEW CONNECTION TO PUBLIC SEWER-(6" PRIVATE SEWER NEEDS TO CONNECT TO A MANHOLE- EITHER NEW OR EXSISTING.) NEED WASTEWATER DESIGN REVIEW OF LIFT STATION- ROBERT BUECHER 617-6206 @ 100 N STONE AV-4TH FL. NEED WASTEWATER 8TH FL CREDIT EVALUATION. 740-6500 |
| 10/11/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved | . |
| 10/12/2004 | DAN CASTRO | ZONING | REVIEW | Denied | Structural plans must be approved by Building Review and site plan must be approved by all sections prior to Zoning approval of structural plans. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/13/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |